Transformer Protection 87T

Differential · Harmonic Restraint · 50/51 · 49 · 24

0/5 steps · 0%

Mission Brief

Protect the Transformer

A 20 MVA, 69/13.8 kV Dyn11 transformer at a FortisBC substation is being re-commissioned after an OLTC overhaul. The previous settings nuisance-tripped on energizing and once let a through-fault rattle the differential. Your job: commission the full transformer protection — the 87T differential done right (vector-group compensation, dual-slope restraint, harmonic blocking) plus the backup, thermal and overexcitation functions — and prove it on the test bench.

  • Understand what the differential measures and why it would false-trip
  • Compensate the vector group and remove zero-sequence
  • Set the dual-slope restraint to ride CT mismatch + tap travel
  • Arm 2nd-harmonic (inrush) and 5th-harmonic (overexcitation) blocking
  • Set the 50/51 backup and prove the scheme on secondary injection
1

What it measures — current in equals current out

A differential element trusts Kirchhoff's law: whatever current flows into the transformer must flow out. It compares the HV and LV currents and watches the difference. Zero difference = healthy or through-fault. A real difference = current is escaping inside the protected zone — an internal fault.

2

Why it would false-trip — three lies

Three things make the two currents look different when nothing is wrong. Each has a fix:

  • CT ratio mismatch + tap changer — the HV and LV CTs never match perfectly, and the OLTC moves the ratio. Fix: the percentage (biased) slope.
  • Vector group — a Dyn transformer phase-shifts the current 30°, so even balanced load looks unbalanced. Fix: phase + zero-sequence compensation.
  • Magnetizing inrush — energize the transformer and a huge one-sided current flows into the HV only. Fix: 2nd-harmonic restraint.
3

The fix — a dual-slope restraint characteristic

Plot differential current against restraint (bias) current. The relay only operates above the line. The first slope rides over CT mismatch and tap travel; the steeper second slope keeps it stable when a heavy through-fault saturates the CTs. Drag the point: internal faults climb into operate, through-faults stay restrained.

OPERATE
restraint I_bias (× In)diff I_diff (× In)

drag the point — operate above the dual-slope line (slope1 20% · slope2 60%)

I_diff
3.00× In
threshold
0.30× In
decision
trip
4

Compensate the vector group first

Before the relay can subtract the two currents it must line them up: correct the clock-number phase shift and strip the zero-sequence off any grounded-wye winding. Numerical relays do this in software once you tell them the vector group.

Vector Group — Dyn11

ABCHV (wye) 0°ABCLV (wye) −-30°-30° phase shift to compensate

Dyn11: compensate the -30° phase shift and remove zero-sequence on the wye side before the differential subtraction.

5

Don't trip on energizing — harmonic restraint

Inrush is rich in 2nd harmonic; overexcitation is rich in 5th. The relay measures the harmonic content of the differential current and blocks when it is high — that is how it tells a fault from a transformer just being switched in. Slide the harmonics and watch the block engage.

Inrush & Overexcitation — Harmonic Restraint

2nd-harmonic (inrush)45% · block ≥ 8%
5th-harmonic (overexcitation)8% · block ≥ 30%
2nd harmonic 45% ≥ 8% → trip BLOCKED (energizing inrush recognised)