Restricted Earth Fault 64

High-Z Differential · Boundary Balance · CT Stability

0/5 steps · 0%

Mission Brief

The Fault Nobody Sees

A 20 MVA transformer's 13.8 kV winding is resistance-grounded through a 20 Ω NGR. A ground fault near the neutral end of the winding makes so little current that the phase differential and the 51N both stay silent while the winding slowly cooks. Your job: commission the Restricted Earth Fault element so it catches that near-neutral fault — yet stays rock-stable when a heavy fault downstream saturates a CT.

  • See REF as a current balance around a restricted zone (Kirchhoff)
  • Understand why external faults cancel and internal faults don't
  • Set the high-impedance stability voltage above a saturated CT (IEEE C37.110)
  • Size the stabilising resistor and confirm CT knee-point ≥ 2·Vs
  • Prove sensitivity to a near-neutral fault and check CT polarity
1

It's a balance around a bag

Forget the name for a second. REF is Kirchhoff's law around a zone: add up every current crossing the boundary — the three phase CTs and the neutral CT. Whatever flows in must flow out. If the sum isn't zero, current is escaping inside the zone.

STABLE
REF protected zone (64)ABCneutralNGRfault
phase resid.
10.00×
neutral CT
10.00×
spill
0.00×
REF
stable

balanced — in equals out

2

Now the name — “restricted”

The protected zone is restricted to the area between the phase CTs and the neutral CT. And it's a differential of the ground current — neutral CT versus the residual of the three phase CTs — not an overcurrent like 51N. That's the whole reason people confuse it.

3

External vs internal — the flip

External fault: the ground current leaves on a phase and returns through the neutral — the two CTs cancel, spill ≈ 0, stable. Internal fault: the current returns to ground inside the zone and never reaches the phase CTs — spill = the neutral current, operate. Toggle it above.

4

Why bother — it sees what nothing else can

A ground fault near the neutral end of the winding drives very little current. The 87T is slope-desensitised and the 51N sits above load, so both go blind down there. REF carries no load current, so it can be set far more sensitively and protect the near-neutral winding everyone else misses.

Winding Coverage — REF vs 51N

How far down the wye winding (toward the neutral) each element can still detect a ground fault. The near-neutral zone makes little current.

REF (64)95% of winding
neutral end →
51N37% of winding
neutral end →

REF protects 95% of the winding versus 51N's 37% — the bottom 58% near the neutral is only covered by REF.

5

The only real enemy — through-fault CT saturation

On a heavy external fault one phase CT can saturate and under-read, creating a false spill. High-impedance REF fixes this with a stabilising resistor and a setting voltage above what a saturated CT can ever produce (and a CT knee-point ≥ 2·Vs). Slide the saturation up and watch the setting hold the line.

High-Impedance Stability (IEEE C37.110)

Vs 40V
floor 135V
Vk 400V
external through-fault CT saturation100% → relay sees 135 V
MIS-OPERATES — saturated CT develops 135 V, above the 40 V setting. Raise Vs.
Vs ≥ stability floor40 ≥ 135 V
Vk ≥ 2·Vs400 ≥ 80 V
Rstab1000 Ω (~2000)
primary op current19 A
6

The modern alternative — biased REF

Numerical relays skip the resistor and use a percentage-slope differential on the residual instead — the same characteristic plane as the 87T, applied to the ground current.

Biased REF restrains with a single percentage slope (20%) above a minimum pickup (0.1× In) — tolerant of CT mismatch, no stabilising resistor. Drag the operating point: internal faults climb into operate, external imbalance stays restrained.

OPERATE
restraint I_bias (× In)diff I_diff (× In)

drag the point — operate above the dual-slope line (slope1 20% · slope2 20%)

I_diff
1.50× In
threshold
0.10× In
decision
trip