Directional Overcurrent 67/67N

Direction by Angle (RCA · Polarizing · Memory)

0/7 steps · 0%

Mission Brief

Which Way Did It Flow?

FortisBC, 25 kV ring bus at the Vernon tie. Two sources back-feed this bus, and last week a fault on the adjacent feeder tripped YOUR healthy tie breaker — a reverse-infeed mis-operation. The plain overcurrent relay couldn't tell the fault was behind it. Your job: commission the directional element (67/67N) so it trips for forward faults and blocks the reverse infeed — and survives a bolted close-in fault that collapses the polarizing voltage.

  • Understand directionality — the relay decides from an ANGLE, not a magnitude
  • Set the RCA/MTA so forward operates and reverse blocks, with margin
  • Choose phase and ground polarizing sources for this grounding/scheme
  • Recognise when memory polarization is mandatory (close-in collapse)
  • Back-calculate TMS and commission with V+I injection at fault angles
1

Direction is an angle, not a magnitude

Every element so far tripped on how much current. This one trips on which way it flows. The relay compares the current against a reference phasor (“polarizing”) and asks a single yes/no question: is the current within ±90° of the maximum-torque line? Drag the current below and watch the decision flip as it crosses the zero-torque boundary.

OPERATE
zero-torqueMTA -75°VpolI

drag the I phasor — operate when it lands within MTA ± 90°

∠I vs Vpol
-75°
∠I vs MTA
Decision
FWD · trip
2

Why you need it — parallel paths

On a radial feeder, current only ever flows one way, so plain 50/51 is enough. The moment you have two sources or parallel feeders, a single fault is fed from both ends. A non-directional relay on the healthy feeder sees that reverse infeed and trips it too — you lose selectivity. The 67 element looks at direction and blocks the reverse-fed relay.

3

The reference — polarizing

“Within ±90° of what?” — of the polarizing reference. The choice depends on the element and the fault:

  • Phase 67 — quadrature (cross-phase) voltage: polarize the faulted phase's current with the other two phases' voltage, which stays healthy for a single fault.
  • Ground 67N — zero-sequence voltage (3V0), zero-sequence current (neutral CT), or negative-sequence (I2/V2). Which one is available depends on the grounding and the VT/CT scheme.
4

The trap — close-in faults collapse Vpol

A bolted three-phase fault right at the relay drives the local voltage toward zero — including the polarizing voltage. With no reference, a plain voltage-polarized element goes blind exactly when it's needed most. The fix is memory polarization: the relay remembers the pre-fault positive-sequence voltage for a few cycles and polarizes against that. If a fault retains very little voltage, memory polarization is mandatory.